4-8 zone Fire Alarm Control Panel
คุณสมบัติ
This conventional fire alarm system is designed based on EN54 part 2&4 standard.
Modularized design which can extend from 1 zone to 4 zones easily.
The conventional fire alarm system has 2 level control mode with a lock
It has FIRE and FAULT signal output, each zone with a fire relay.
It has 24VDC and 5VDC power supply output.
It has 2 general sounders output.
Each zone has 1 circuit detector input.
Each zone can be disabled by a button.
Has a RESET button to reset the panel.
Has a SILENCE button to stop BUZZER and SOUNDERS.
It has an EVACUATE button to start a manual fire alarm immediately.
It has a battery low protection function, when the battery voltage is lower than 21VDC, the battery will be cut off automatically until the main power is on.
The conventional fire alarm system has an optional GSM module for fire alarm by SMS 14. It is economical, user‐friendly, and easy maintenance.

รายละเอียด
Power specification  | Mains supply voltage 110VAC or 240VAC Internal power supply 27.2VDC total output current limited 3A @ 240VAC  | 
Main supply monitor for fault  | Yes  | 
Each zone fire relay  | Yes  | 
Battery protection for low-voltage  | Yes  | 
Battery (default configuration)  | 12V 24Ah x 2  | 
Detector circuit configuration  | Number 2 of circuit  | 
Line fault monitor circuit for open circuit  | Yes  | 
Line fault monitor circuit for short circuit  | Yes  | 
Line fault monitor for detector removal  | Yes  | 
Call point resistor value  | 470 to 680 Ω, 0.225 or 0.5 watt  | 
Maximum number of smoke/heat detectors per zone  | 20 (based on a total detector current of 2mA, each detector consuming 100μA)  | 
Maximum number of manual call points per zone  | No limit  | 
Sounder circuit specification  | Number of general circuits2  |