top of page

SFP-2404 4-Zone Control

คุณสมบัติ

The SFP-2404 is UL Edition listed conventional fire alarm control panels with two alarm initiating zones and four initiating zones respectively. The Notification Appliance Circuit (NAC) protocol can silence audible devices while strobes continue to flash, using a single pair of wires.

Features & Benefits:

  • Compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, water flow devices, tamper switches, and other normally open contact devices

  • 4-zone: 4 Class By/Style B zones (Class A/Style D optional); 2 Class B/Style Z (Class A/Style Z optional)

  • 3 Amps (expandable to 6.0 AMPS on 4-zone) with programmable strobe synchronization

SFP-2404 4-Zone Control

รายละเอียด

AC POWER — TB3

  • SFP-2404: 120 VAC, 50/60 Hz, 2.3 A. 

  • SFP-2404E: 240 VAC, 50 Hz, 1.15 A.

  • Wire Size: Minimum 14 AWG (2.0 mm2) with 600 V insulation. 


BATTERY (SEALED LEAD-ACID ONLY) — J8 

  • Maximum charging circuit: normal flat charge 27.6 VCD @ 0.8 A

  • Maximum battery charger capacity: 18.0 AH battery (two 7.0 AH batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Notifier BB-17). 


INITIATING DEVICE CIRCUITS — TB3 

  • Alarm zones 1 - 4

  • Power-limited circuitry.

  • Operation: all zones Style B (Class B). 

  • Normal operating voltage: nominal 20 VDC. 

  • Alarm current: 15 mA minimum. 

  • Short-circuit current: 40 mA maximum. 

  • Maximum loop resistance: 100 ohms. 

  • End-of-line resistor: 4.7K ohm, 1⁄2 watt (P/N 71252). 

  • Standby current: 4 mA. 

  • Compatible devices: refer to the Notifier Device CompatibilityDocument PN 15378 for a complete list of compatible devices. 


NOTIFICATION APPLIANCE CIRCUITS — TB2 

  • Two NACs. 

  • Power-limited circuitry. 

  • Normal operating voltage: nominal 24 VDC. 

  • Maximum signaling current: 2.5 A total with standard trans-former 5.0 A total (2.5 A maximum per NAC) with optionaltransformer. 

  • End-of-line resistor: 4.7K ohm, 1⁄2 watt (P/N 71252). 

  • Compatible devices: refer to the Notifier Device CompatibilityDocument PN 15378 for a complete list of compatible devices. 

  • Power-limited circuitry.

  • Normal operating voltage: nominal 24 VDC. 

  • Maximum signalling current: 2.5 A total with standard trans-former 5.0 A total (2.5 A maximum per NAC) with optionaltransformer. 

  • End-of-line resistor: 4.7K ohm, 1⁄2 watt (P/N 71252). 

  • Compatible devices: refer to the Notifier Device CompatibilityDocument PN 15378 for a complete list of compatible devices. 


FORM-C RELAYS 

  • Trouble Relay TB5 (fail-safe). 

  • Alarm Relay TB6. 

  • Supervisory relay TB7. 

  • Relay contact ratings: 2.0 A @ 30 VDC (resistive). 


AUXILIARY OUTPUT: RESETTABLE POWER — TB1 

  • Operating voltage: nominal 24 VDC. 

  • Maximum available current: 500 mA — appropriate for pow-ering four-wire smoke detectors (see notes).

  • Power-limited circuitry.


CABINET DIMENSIONS 

  • Door: 15.342” (38.97 cm) high x 14.667” (37.28 cm) wide x 0.375” (0.95 cm) deep.

  • Backbox: 15.0” (38.10 cm) high x 14.5” (36.83 cm) wide x 3.0” (7.62 cm) deep.


BACKBOX MOUNTING 

  • The cabinet can be surface mounted. The door is removable during installation by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional 0.25” diameter holes at the bottom.

Group 4.png

ที่อยู่

29 พหลโยธิน 52 ถนนพหลโยธิน คลองถนนสายไหม กรุงเทพมหานคร 10220

โทร:
02-972-0756-9

ฝ่ายขาย:
sales@msupplyinter.com

เวลาเปิดทำการ

โทรสาร:
02-552-4952

ติดต่อทั้วไป:
msupply@truemail.co.th

จันทร์ - ศุกร์

9:00 น. – 17:00 น.

เสาร์

9:00 น. – 15:00 น.

Copyright © 2023 M.SupplyInter (Thailand) .Co.LTD

bottom of page